1–7

Overview of the CFM Module

Publication 1771Ć6.5.99 - December 1995

The CFM module has four assignable outputs. These outputs are
designed for applications that require fast response. The outputs:

are electrically fused/current limited to 3A (output combinations
are limited to 7A)

can be assigned to any input channel with user-selectable turn-on
and turn-off values

are current sourcing at 5-40V dc (1A maximum per output)

must be connected to an external power supply

are in groups of two — this lets you use two separate external
power supplies if desired (one for outputs 0&1 and one for
outputs 2&3)

Outputs may be forced on or off independent of count or
frequency value. They may be forced on and off by setting bits in the
BTW configuration block.

Important: You can assign as many as four outputs to a given

channel; however, you can not use the same output with
two different channels.

In this mode

of operation

You can assign outputs that are programmable to trigger

Totalizer

on total, rate, rate change (acceleration), total overflow or

prover status

Nonresettable Totalizer on total, rate, rate change (acceleration), total overflow or

prover status

HighĆresolution
Frequency

on frequency or frequency rate of change (acceleration)

Direction Sensor

on either CLOCKWISE or COUNTERĆCLOCKWISE direction,

acceleration or frequency (outputs are triggered ON only)

Output Capabilities