beautypg.com

Btw configuration block, Btw word description key – Rockwell Automation 1771-CFM,D17716.5.99 CONFIGURABLE FLOWMET User Manual

Page 36

background image

4–2

Configure the CFM Module

Publication 1771Ć6.5.99 - December 1995

BTW Configuration Block

Word(s)

Bit

Word(s)

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Block ID & Resets

1

Header

Prover Run Initialize

Overflow Reset

Total Reset

Output 1 and Output 0 Trigger & Select

2

Output 1 Trigger

Tie Output 1 to Channel

Output 0 Trigger

Tie Output 0 to Channel

Output 3 and Output 2 Trigger & Select

3

Output 3 Trigger

Tie Output 3 to Channel

Output 2 Trigger

Tie Output 2 to Channel

Input Channel Operating Mode

4

Channel 3

Channel 2

Channel 1

Channel 0

Input Channel Configuration

Channel 0 (words 5Ć14)

Channel 1 (words 15Ć24)

Channel 2 (words 25Ć34)

Channel 3 (words 35Ć44)

5, 15, 25, 35

Frequency

in 10ths

Bandwidth

Limit

Sampling

Termination

4 x

High Hz

Prover

Type

ЙЙЙЙ

Й

ЙЙ

Й

ЙЙЙЙ

Debounce

Filtering

Acceleration Calculation Time

6, 16, 26, 36

Minimum Frequency Sampling Time

7, 17, 27, 37

Number of Pulses to Terminate Sampling

8, 18, 28, 38

Highest Allowable Frequency

9, 19, 29, 39

Acceleration Alarm Value (what rate to trigger on)

10, 20, 30, 40

Frequency Scaler Multiplier

Frequency Scaler Divisor

11, 21, 31, 41

Total Scaler Multiplier

12, 22, 32, 42

Total Scaler Divisor

13, 23, 33, 43

Rollover Value Ċ Most Significant Digit (0Ć999 x 10,000)

14, 24, 34, 44

Rollover Value Ċ Least Significant Digit (0Ć9,999)

Output Configuration

Output 0 (words 45Ć48)

Output 1 (words 49Ć52)

Output 2 (words 53Ć56)

Output 3 (words 57Ć60)

45, 49, 53, 57

Output ON value Ċ Most Significant Digit (0Ć999 x 10,000)

46, 50, 54, 58

Output ON value Ċ Least Significant Digit (0Ć9,999)

47, 51, 55, 59

Output OFF value Ċ Most Significant Digit (0Ć999 x 10,000)

48, 52, 56, 60

Output OFF value Ċ Least Significant Digit (0Ć9,999)

Valid BTW lengths are: 0, 1, 2, 3, 4, 14, 24, 34, 44, 48, 52, 56, 60.

ALL numeric values are in binary.

➂ When scaling is used, all outputs are still controlled by the actual value not the scaled value.

BTW Word Description Key

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Bits

Mode(s) that use these bits.

Description of what these bits are used for.

word #

Mode abbreviations:

Totalizer = T

Nonresettable Totalizer = NRT

HighĆresolution Frequency = HR

Direction Sensor = DS