Rockwell Automation 1771-CFM,D17716.5.99 CONFIGURABLE FLOWMET User Manual
Page 40
![background image](/manuals/579761/40/background.png)
4–6
Configure the CFM Module
Publication 1771Ć6.5.99 - December 1995
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Total Scaler
➀
Divisor Ċ the total value
returned in the BTR is divided by the
specified value.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
T, NRT
Rollover Value Ċ the count value that
the totalizer will reset or rollover to 0 at.
T, NRT
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
MSD - ranges from
0Ć999 x 10,000
LSD Ć ranges from 0Ć9,999
RANGE: 0 Ć 9,999,999
DEFAULT: 0 (which is rollover of 10,000,000)
RANGE: 0 Ć 32,767 DEFAULT: 1
Important: The Total Scaler Multiplier must be
≤
Total Scaler Divisor.
See Total Scaler Multiplier.
word 12 (channel 0)
word 22 (channel 1)
word 32 (channel 2)
word 42 (channel 3)
word 13 (channel 0)
word 23 (channel 1)
word 33 (channel 2)
word 43 (channel 3)
word 14 (channel 0)
word 24 (channel 1)
word 34 (channel 2)
word 44 (channel 3)
Important: The Rollover Value must be
≥
(actual frequency x 10ms).
If you are using the prover function, the expected Prover
Total Count Value (BTR words 13/14, 22/23, 31/32, or
40/41) must be < Rollover Value.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Total Scaler
➀
Multiplier Ċ the total
value returned in the BTR is multiplied by
the specified value.
T, NRT
word 11 (channel 0)
word 21 (channel 1)
word 31 (channel 2)
word 41 (channel 3)
RANGE: 0Ć32,767
DEFAULT: 1
Important: The Total Scaler Multiplier must be
≤
Total Scaler Divisor.
See Total Scaler Divisor.
➀
When scaling is used, all outputs are still controlled by the actual value not the scaled value.
➀
When scaling is used, all outputs are still controlled by the actual value not the scaled value.