Rockwell Automation 1771-CFM,D17716.5.99 CONFIGURABLE FLOWMET User Manual

Page 40

background image

4–6

Configure the CFM Module

Publication 1771Ć6.5.99 - December 1995

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Total Scaler

Divisor Ċ the total value

returned in the BTR is divided by the

specified value.

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

T, NRT

Rollover Value Ċ the count value that

the totalizer will reset or rollover to 0 at.
T, NRT

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

MSD - ranges from

0Ć999 x 10,000

LSD Ć ranges from 0Ć9,999

RANGE: 0 Ć 9,999,999

DEFAULT: 0 (which is rollover of 10,000,000)

RANGE: 0 Ć 32,767 DEFAULT: 1
Important: The Total Scaler Multiplier must be

Total Scaler Divisor.

See Total Scaler Multiplier.

word 12 (channel 0)

word 22 (channel 1)

word 32 (channel 2)

word 42 (channel 3)

word 13 (channel 0)

word 23 (channel 1)

word 33 (channel 2)

word 43 (channel 3)

word 14 (channel 0)

word 24 (channel 1)

word 34 (channel 2)

word 44 (channel 3)

Important: The Rollover Value must be

(actual frequency x 10ms).

If you are using the prover function, the expected Prover

Total Count Value (BTR words 13/14, 22/23, 31/32, or

40/41) must be < Rollover Value.

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Total Scaler

Multiplier Ċ the total

value returned in the BTR is multiplied by

the specified value.

T, NRT

word 11 (channel 0)

word 21 (channel 1)

word 31 (channel 2)

word 41 (channel 3)

RANGE: 0Ć32,767

DEFAULT: 1

Important: The Total Scaler Multiplier must be

Total Scaler Divisor.

See Total Scaler Divisor.

When scaling is used, all outputs are still controlled by the actual value not the scaled value.

When scaling is used, all outputs are still controlled by the actual value not the scaled value.