beautypg.com

C-10, Interpret status indicators, Additional feature – Rockwell Automation 1771-CFM,D17716.5.99 CONFIGURABLE FLOWMET User Manual

Page 74: Ttl inputs (5-40v dc)

background image

Replace Your QRC Module

C–10

Publication 1771Ć6.5.99 - December 1995

Interpret Status Indicators

Indicators

If indicator

Is ON

Is OFF

ACTIVE

the CFM module is receiving power and

operational

a. Check FAULT LED Ċ if on, follow the

steps listed under if FAULT is ON.

b. Check power supply LEDs.

INPUTS

(F0 & F2)

F0 - flashes with pulses at Channel A

F2 - flashes with pulses at Channel B

a signal is not present at the designated

input terminal (low)

ACTIVE

INPUTS/OUTPUTS

F0 F1 F2 F3

G0 G1 G2 G3

O0 O1 O2 O3

OUTPUTS

(O0 & O1)

O0 - indicates Channel A frequency

is

15,800Hz

O1 - indicates Channel B frequency

is

15,800Hz

the output is off

S S S S

STATUS

O0 O1 O2 O3

STATUS

S3

BTR is occurring

BTR is not occurring

S0 S1 S2 S3

S4 S5 S6 S7

FAULT

STATUS

FAULT

1. Turn off power to the I/O chassis

backplane and wiring arm.

2. Reseat the CFM (QRC) module in

the I/O chassis.

3. Restore power to the I/O chassis

backplane and wiring arm.

Important: If the fault LED remains on,

there may be an internal problem.

Contact your local AllenĆBradley

representative for additional assistance.

normal operation

All other LED's are OFF in normal operation.

Outputs are not active if PLC processor is faulted or in Program mode.

Additional Feature

When you replace your existing QRC module with the CFM module,
you can set input channel jumpers for:

TTL inputs (5-40v dc)

500mV ac sensitivity for improved noise immunity

For additional information on setting the input channel jumpers, see:

Install the

CFM Module

2