Make connections to the new wiring arm – Rockwell Automation 1771-CFM,D17716.5.99 CONFIGURABLE FLOWMET User Manual

Page 80

background image

Replace Your QRD Module

D–6

Publication 1771Ć6.5.99 - December 1995

Connect your I/O devices to the 40-terminal field wiring arm
(cat. no. 1771-WN) shipped with the CFM module. Use the wiring
examples on page D–7 for additional assistance on connecting
your devices.

F0 Input

F1 Input

F2 Input

F3 Input

actual wiring runs in this direction

Even Numbered Terminals 2Ć40

Odd Numbered Terminals 1Ć39

NEW wiring arm (1771ĆWN)

OLD wiring arm (1771ĆWG)

not used
not used
Channel 1 +
Channel 1 -
shield
Channel 2 +
Channel 2 -
shield
Channel 3+
Channel 3 -
shield
Channel 4 +
Channel 4 -
shield
not used
not used
TTL
not used
Channel 3, 4 level
Channel 1, 2 level
not used

18322

F0 (TTL)

F0 RET
F1 (TTL)
F1 RET

F2 (TTL)
F2 RET
F3 (TTL)
F3 RET

2
4
6
8

10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40

1
3
5
7
9

11
13
15
17
19
21
23
25
27
29
31
33
35
37
39

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

To use a channel in TTL, jumper the appropriate TTL pin to the appropriate

RET. To use Channel 1 in TTL, jumper pin 9 to pin 11.

The sensor cable must be shielded. The shield:

must extend the length of the cable, but be connected

only at the 1771 I/O chassis

must extend up to the point of termination

Important: The shield should extend to the termination point,

exposing just enough cable to adequately terminate the

inner conductors. Use heat shrink or another suitable

insulation where the wire exits the cable jacket.

Make Connections to the

New Wiring Arm