General specifications – Rockwell Automation 1771-CFM,D17716.5.99 CONFIGURABLE FLOWMET User Manual
Page 60
Specifications
A–2
Publication 1771Ć6.5.99 - December 1995
Number of Input Channels
4
Module Location
1771ĆA1B, ĆA2B, A3B, ĆA3B1, ĆA4B (series A and B)
I/O chassis
1771ĆAM1, ĆAM2 I/O chassis with integral power supply,
adapter
Maximum Count Value
0-9,999,999 (programmable)
BTW Processing Time (worst case)
5.5ms Ċ on a configuration change
Module Scan Time
1.3-5ms (depending on configuration and frequency)
Maximum Input Frequency
100kHz @ flowmeter Input (maximum frequency is 120kHz Ć
100kHz @ gate input overrange occurs at 100kHz)
Inputs per Channel
2 - flowmeter input Ċ used for all modes
gate input Ċ used in Totalizer and Nonresettable
Totalizer modes
Input Voltage
50mVĆ200V ac peak Ċ Magnetic Pickup
5Ć40V dc (TTL compatible)
Bently 3300 5 & 8 mm Ċ Proximity Pickups
Input Impedance
5K
Ω ±
30% resistive
Number of Outputs
4
Maximum Output OffĆstate Leakage Current
less than 300
µ
A @ 40V dc
Maximum OnĆstate Voltage Drop
0.6
Ω
x current
Output Control
Any number of outputs are assignable to any of 4 channels.
One turn-on" value and one turn-off" value per output.
Output Voltage
5 to 40V dc, customer supplied
Output Current
1A per channel sourced out of module
All outputs can be on simultaneously without derating.
Output Switching Time
outputs triggered by Total: turn ON < 100
µ
s; turn OFF < 100
µ
s
all other turn ON and OFF times < 1ms
Filtering (F0ĆF3 inputs)
Ċ jumper selectable
highĆspeed or lowĆpass filter jumper (filter = below 70Hz)
Debouncing (G0ĆG3 inputs)
Ċ software selectable
1s (approximate) between transitions with no minimum pulse
width Ċ Totalizer and Nonresettable Totalizer modes only
+24V dc Source
ripple:
±
5%; noise: 240mV peakĆtoĆpeak
Backplane Current
1A maximum
Isolation Voltage
500V between input and backplane
1500V between output and backplane
500V between isolated channels
1500V between isolated outputs and gates
Power Dissipation
13W (maximum); 2W (minimum)
Thermal Dissipation
54.2 BTU/hr (maximum); 6.8 BTU/hr (minimum)
Input Conductors
Wire Size
Category
Length
Belden 8761
Category 2
1
304.8m (1000ft)
Output Conductors
Wire Size
Category
Belden 8761
Category 1
➀
Environmental
Operating Temperature
Conditions
Storage Temperature
Relative Humidity
0 to 60
o
C (32 to 140
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% (without condensation)
Field Wiring Arm
40-terminal (cat. no. 1771-WN)
Wiring Arm Screw Torque
7Ć9 inchĆpounds
Keying (lower backplane connector)
between 2 and 4
between 6 and 8
Agency Certification
(when product or packaging is marked)
ОО
ОО
ОО
ОО
О
О
О
О
marked for all applicable directives
Class 1 Div 2 Hazardous
➁
➀
Use this conductorĆcategory information for planning conductor routing as described in the systemĆlevel installation manual.
➁
CSA certificationĊ Class I, Division 2, Group A, B, C, D or nonhazardous locations.
General Specifications