Input capabilities – Rockwell Automation 1771-CFM,D17716.5.99 CONFIGURABLE FLOWMET User Manual

Page 14

background image

1–4 Overview of the CFM Module

Publication 1771Ć6.5.99 - December 1995

The CFM module accepts input for up to four channels
(mode dependent). Each of the four input channels may accept these
input signals:

magnetic pickup — 50mV to 200V ac peak (optional 500mV to
200V ac peak for improved noise immunity)

4-40V dc pulses with open collector (TTL compatible)

proximity probe inputs

compatible with Bently Nevada 3300 (5mm and 8mm)
proximity transducer systems

provides two isolated 24V dc power supplies (rated at 12mA)
to power external devices

You configure the CFM module’s four input channels for your
specific application(s). Each input channel has two input selections:

Channel 0

Channel 1

Channel 2

Channel 3

flowmeter input (F0)

gate input (G0)

flowmeter input (F1)

gate input (G1)

flowmeter input (F2)

gate input (G2)

flowmeter input (F3)

gate input (G3)

flowmeter input (F0ĆF3) Ċ you connect

your input device to this input (ac, TTL)

gate input (G0ĆG3) Ċ accepts 4Ć40V dc

input pulse from open collector or external

contact closure. Used in Totalizer and

Nonresettable Totalizer modes to:

store the current count of an input channel

upon impulse on gate

interface to a prover when a prover is

enabled Ċ used to store the count as the

spheroid is sensed in the prover tube

four input channels

See pages 2-9 and 2-10 for wiring diagrams.

Input Capabilities