Troubleshoot the CFM Module

Use this chapter to troubleshoot the CFM module by interpreting the:

status indicators

diagnostic word in the BTR file

The CFM module provides these LED indicators:

Indicators

If indicator

Is ON

Is OFF

ACTIVE

the CFM module is successfully receiving

power and operational

a. Check FAULT LED Ċ if on, follow the steps

listed under if FAULT is ON.

b. Check the power supply.

INPUTS

(F0ĆF3 & G0ĆG3)

a signal is present at the designated

input terminal

a signal is not present at the designated

input terminal

OUTPUTS

(O0ĆO3)

the module has commanded an output on

the output is off

ACTIVE

INPUTS/OUTPUTS

STATUS

F0 F1 F2 F3

G0 G1 G2 G3

O0 O1 O2 O3

S1

STATUS

S2
S3

PowerĆup Bit (BTR word 1, bit 00) is ON

(=1) Ċ BTW hasn't occurred since

powerĆup, or invalid BTW, or

PLC processor in Program mode

BTW is occurring
BTR is occurring

PowerĆup Bit (BTR word 1, bit 00) is OFF (=0) Ċ

valid BTW has occurred since powerĆup or since

last switched from Program to Run mode

BTW is not occurring
BTR is not occurring

S0 S1 S2 S3

S4 S5 S6 S7

FAULT

STATUS

FAULT

1. Turn off power to the I/O chassis

backplane and wiring arm.

2. Reseat the CFM module in the I/O

chassis.

3. Restore power to the I/O chassis

backplane and wiring arm.

Important: If the fault LED remains on,

there may be an internal

problem. Contact your local

AllenĆBradley representative

for additional assistance.

normal operation

What This Chapter

Contains

Status Indicators