beautypg.com

Rockwell Automation 1771-CFM,D17716.5.99 CONFIGURABLE FLOWMET User Manual

Page 43

background image

4–9

Configure the CFM Module

Publication 1771Ć6.5.99 - December 1995

Frequency Sampling

In the Totalizer and Nonresettable Totalizer modes, the CFM module
begins a frequency sample arbitrarily and ends the sampling within
1ms after the sampling time has expired and one pulse has been
detected. You can use Bandwidth Limit to exert control over the
CFM module’s frequency sampling.

In these modes, the CFM module calculates frequency based on
these values:

Value

BTW word #

Use to

specify the minimum time the CFM module will spend collecting

pulses to determine a frequency. The time period begins arbitrarily,

not on a leading edge of a pulse.

Minimum Frequency Sampling Time

6, 16, 26, 36

Frequency is calculated after a pulse occurs and the time has

expired. The total time is measured and used with the sampled

counts to determine a frequency. This frequency value is in BTR

word 7/8, 16/17, 25/26 or 34/35.
As the actual frequency decreases, the actual sample time will

increase (for frequencies < 1Hz, it can take as long as 2s to

calculate the frequency). See Bandwidth Limit.

Bandwidth Limit

5, 15, 25, 35 (bit 14)

control the maximum time the CFM module spends calculating a

frequency and the minimum frequency that can be read by the

CFM module.
If ON: limits the maximum time period to 2 x Minimum Frequency

Sampling Time and minimum frequency to 1/Minimum Frequency

Sampling Time.
If OFF: maximum time period is 2s, minimum frequency is 1Hz.

Acceleration Calculation Time

5, 15, 25, 35 (bits 00Ć09)

specify the number of frequency samples the CFM module will

spend to calculate the acceleration value. The default value (0) will

calculate a rolling average of the previous five samples.
Since the frequency sample time may vary, so does the actual

acceleration calculation time.

Acceleration Alarm

9, 19, 29, 39

determine the acceleration value that, if exceeded, will activate the

BTR Acceleration Alarm (word 4 & 5, bits 00 & 08).

RANGE: 0Ć32,767
The CFM module will not calculate an acceleration if

this acceleration value is zero.

Frequency Multiplier/Divisor

10, 20, 30, 40

scale the returned frequency and acceleration to actual engineering

units. Frequency Multiplier must be < Frequency Divisor.

For each value RANGE: 0Ć255 DEFAULT: 0 (= 1

no scaling)

The scaled frequency/acceleration values can not be used to

trigger any outputs (outputs triggered by frequency/ acceleration

are triggered by actual frequency/acceleration).

Highest Allowable Frequency

8, 18, 28, 38

specify the highest frequency value allowed on the input channel.

When this value is exceeded, the input channel's overspeed alarm

will activate.
This value is also used in calculating Percent of Full Scale

(BTR, word 6, 15, 24 or 33).

Bandwidth Limit

(word 5, bit 14)

set (ON)?

N

Y

and no pulses are

received after the

sampling time expires,

the frequency is

calculated up to 2s after

the initial pulse and will

measure frequencies as

low as 1Hz.

and no pulses are received

within one more sample

time, the frequency will

then be calculated. The

minimum frequency is then

1/Minimum Frequency

Sampling Time and the

maximum time period is

2 x Minimum Frequency

Sampling Time.