Install the CFM Module

Publication 1771Ć6.5.99 - December 1995

Your CFM module receives its power through the 1771 I/O chassis
backplane from the chassis power supply. The maximum current
drawn by the CFM module is 1.0A.

Add this value to the requirements of all other modules in the I/O
chassis to prevent overloading the chassis backplane and/or
backplane power supply.

!

ATTENTION: When using a 1771-P7 or 1771-PS7
power supply to power an I/O chassis, you cannot
place more than four CFM modules in this chassis.

The interaction between the four CFM modules and the
1771-P7 or 1771-PS7 power supply (not 16A limit)
prevents the power supply from powering up.

You check or set these jumpers:

module operation jumper

input channel jumpers

Check the Module Operation Jumper

Important: Make sure the module operation jumper is in the

CFM position (default setting).

CFM

QRD

QRC

19807

If The Jumper Is

Set In This Position

The CFM Module

Will Operate As

QRC

a QRC module (no BTW / 3 word BTR)

QRD

a QRD module (1 word BTW / 9 word BTR)

Calculate Power

Requirements

Set the Configuration

Jumpers