Schematics

B–2

Publication 1771Ć6.5.99 - December 1995

Signal characteristics

50mV threshold

Input

50mV threshold

Turbine flowmeter or magnetic pickup

F0

F1

F2

F3

Turbine flowmeter or magnetic pickup

(50mVĆ142V ac rms)

The signal:

12

16

24

28

+ turbine flowmeter or magnetic pickup

The signal:

should be approximately sinusoidal

must be ac

11

15

23

27

- turbine flowmeter or magnetic pickup

must be ac

must be > 100mV and < 400V

F0 RET

F1 RET

F2 RET

F3 RET

us be

00

a d

00

peakĆtoĆpeak

Input Return

500mV threshold

Input

Turbine flowmeter or magnetic pickup

F0

F1

F2

F3

Turbine flowmeter or magnetic pickup

(500mVĆ142V ac rms)

The signal:

h ld b

i t l i

id l

10

14

22

26

500mV Ċ connect to each corresponding RET

should be approximately sinusoidal

must be ac

must be > 1V and < 400V

12

16

24

28

+ turbine flowmeter or magnetic pickup

must be > 1V and < 400V

peakĆtoĆpeak

11

15

23

27

- turbine flowmeter or magnetic pickup

F0 RET

F1 RET

F2 RET

F3 RET

Input Return

1.3V threshold (TTL)

Input

(

)

Compatible with open collector.

F0

F1

F2

F3

Compatible with open collector.
The signal should be dc pulses with

width > 4us.

9

13

21

25

1.3V (TTL) Ċ connect to each corresponding RET

The TTL mode is compatible with TTL,

4000 series CMOS, and most 0Ć24V

systems The TTL mode in not

12

16

24

28

+ logic circuit

systems. The TTL mode in not

compatible with any signal format with

dc pulses riding on a fixed dc level > 1.3V.

11

15

23

27

- logic GND

p

g

F0 RET

F1 RET

F2 RET

F3 RET

Input Return

12" V threshold (+24V RET)

Input

This specialized mode is compatible with

signal format with pulses riding on a fixed

F0

F1

F2

F3

signal format with pulses riding on a fixed

dc level > +1.3V.
Example

Bently Nevada Proximity Pickup Series

12

12

16

24

28

+ proximity pickup (active sensor)

Bently Nevada Proximity Pickup Series

3300 (5mm and 8mm) where the active"

sensor signals are with a 5V offset.

The signal resides between 5Ć18V

18

18

20

20

- proximity pickup (active sensor)

The signal resides between 5Ć18V,

therefore, it passes through the threshold

of 12"V as referenced to the

S0 RET

S1 RET

S2 RET

S3 RET

of 12"V as referenced to the

+24V dc RET.

Input Return

#

wiring arm terminal number

Signal threshold (500mV or 1.3V) is selected by jumpering the appropriate level to the appropriate RET.