Chapter 3 I/O Memory Mapping

1769-IG16

The following I/O memory mapping lets you configure the 1769-IG16 module.

Input Data File

For each module, slot

x, word 0 in the input data file contains the state of the

module’s input points. The module implements inverted logic on the TTL
inputs. A logix low-input voltage results in the corresponding Input Data File bit
being set to 1. A logic high-input voltage results in the corresponding bit being
cleared to 0.

Enable
Channel

Enable

1

Disable

0

Input
Range
Select

-10…+10V

0

0

0

0

0…5V

0

0

0

1

0…10V

0

0

1

0

1…5V

0

0

1

1

Input Data
Format
Select

Proportional
Counts

0

0

0

Engineering
Units

0

0

1

Scaled for
PID

0

1

0

Percent
Range

0

1

1

Define

To Choose

Make these bit settings