81

I/O Memory Mapping Chapter 3

The bits are defined as follows:

• SGN = Sign bit in 2’s complement format.
• Nu = Not Used. Bit set to 0.
• Sx = General Status bit for input channels 0…15.
• Ox = Over range flag bits for input channels 0…15.
• Ux = Under range flag bits for input channels 0…15.
• Hx = High Alarm flag bits for input channels 0…15.
• Lx = Low Alarm flag bits for input channels 0…15.

Output Data File

For each module, slot

x, words 0 and 1 in the output data file contain the cancel

latched channel alarm control bits.

The bits are defined as follows:

• CLHx = Cancel High Process Alarm Latch for Input x. Allows each input

high-process-alarm latch to be individually cancelled. Cancel = 1.

• CLLx = Cancel Low Process Alarm Latch for Input x. Allows each input

low-process-alarm latch to be individually cancelled. Cancel = 1.

Configuration Data File

The manipulation of bits from this file is normally done with programming
software, such as RSLogix 500, RSLogix 5000, or RSNetWorx for DeviceNet
software, during initial configuration of the system. In that case, graphical screens
provided by the programming software simplify configuration.

Wo

rd

Bit Position

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

0

CLL
7

CLH
7

CLL
6

CLH
6

CLL
5

CLH
5

CLL
4

CL
H4

CLL
3

CL
H3

CLL
2

CL
H2

CL
L1

CL
H1

CL
L0

CL
H0

1

CLL
15

CLH
15

CLL
14

CLH
14

CLL
13

CLH
13

CLL
12

CL
H1
2

CLL
11

CL
H1
1

CLL
10

CL
H1
0

CL
L9

CL
H9

CL
L8

CL
H8