Module configuration word, 1769-it6, Input data file – Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 104

104
Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 3 I/O Memory Mapping
Module Configuration Word
Word 6 of the configuration data file contains the Enable/Disable Cyclic
Calibration bit as shown in the table below.
1769-IT6
The following I/O memory mapping lets you configure the 1769-IT6 module.
Input Data File
The input data file contains the analog values of the inputs.
The bits are defined as follows:
• Sx = General status bit for channels 0…5 and CJC sensors (S6 and S7).
This bit is set (1) when an error (over-range, under-range, open-circuit, or
input data not valid) exists for that channel. An ‘input data not valid’
condition is determined by the user program. This condition occurs when
the first analog-to-digital conversion is still in progress, and after a new
configuration has been sent to the module. Refer to the Compact I/O
Thermocouple/mV Input Module User Manual
1769-
UM004
for additional details.
To Select
Make these bit settings
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Enable/
Disable
Cyclic
Calibration
Enabled
(1)
(1) When enabled, an autocalibration cycle is performed on all enabled channels every 5 minutes.
0
Disabled
1
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Analog Input Data Channel 0
1
Analog Input Data Channel 1
2
Analog Input Data Channel 2
3
Analog Input Data Channel 3
4
Analog Input Data Channel 4
5
Analog Input Data Channel 5
6
OC7
OC
6
OC
5
OC
4
OC
3
OC
2
OC
1
OC
0
S7
S6
S5
S4
S3
S2
S1
S0
7
U0
O0
U1
U0
U2
O2
U3
O3
U4
O4
U5
O5
U6
O6
U7
O7