Chapter 3 I/O Memory Mapping
Fault Value Word
The fault value word, word 4, is used to program the fault state value (0=Off,
1=On). Each output is individually configurable for on or off.
Program to Fault Enable Bit (PFE)
Word 0, bit 0, allows the selection of which data value, the program or fault value,
to apply to the output if a system in Program mode undergoes a system fault,
resulting a change to Fault mode.
Module Default Condition
The module’s default condition is all zeros, programming the conditions shown.
1769-OF2
The following I/O memory mapping lets you configure the 1769-OF2 module.
Input Data File
For each module, slot
x, input data file words 2 and 3 contain the state of the
module’s output data (output data echo) file words 0 and 1. During normal
operation, these input words represent the analog values that the outputs are
directed to by the control program. They are also dependent upon these
configurations:
• Program mode configuration, if supported by the controller
• Fault mode configuration, if supported by the controller
Value
Bit Setting
Off
0
On
1
Value Applied
Bit Setting
Program
0
Fault
1
Word or Bit Affected
Condition Applied
Word 0, Bit 0
Program-to-fault Enable
Program value
Word 1
Program state
User-defined safe state
Word 2
Program value
Off
Word 3
Fault state
User-defined safe state
Word 4
Fault value
Off