Chapter 3 I/O Memory Mapping

Words 0……3 of the configuration file allow you to change the parameters of each
channel independently. For example, word 0 corresponds to channel 0.

Define

To Select

Make these bit settings

15

14

13

12

11

10

9

8

4…
7

3

2

1

0

Input Filter
Selection/-3 dB
Frequency

60 Hz/15.7 Hz

No

t U

se

d

0

0

0

0

50 Hz/13.1 Hz

0

0

0

1

Not Used

0

0

1

0

250 Hz/65.5 Hz

0

0

1

1

500 Hz/131Hz

0

1

0

0

Spare

(1)

(1) An attempt to write any nonvalid (spare) bit configuration into any selection field results in a module

configuration error.

Input Type/
Range

-10 to +10V dc

0

0

0

0

0 to 5V dc

0

0

0

1

0 to 10V dc

0

0

1

0

4 to 20 mA

0

0

1

1

1 to 5V dc

0

1

0

0

0 to 20 mA

0

1

0

1

Spare

(1)

Input Data
Format

Raw/Proportional
Data

0

0

0

Engineering
Units

0

0

1

Scaled-for-PID

0

1

0

Percent Range

0

1

1

Spare

(1)

Enable Channel Enabled

1

Disabled

0