I/O Memory Mapping Chapter 3

Output Data File

For each input module, slot

x, word 0 in the output data file contains alarm

unlatch control bits.

The bits are defined as follows:

• CLHx = Cancel High Process Alarm Latch for Input x. Allows each input

high-process-alarm latch to be individually cancelled. Cancel = 1.

• CLLx = Cancel Low Process Alarm Latch for Input x. Allows each input

low-process-alarm latch to be individually cancelled. Cancel = 1.

Configuration Data File

The manipulation of the bits from this file is normally done with programming
software, such as RSLogix 500, RSLogix 5000, or RSNetWorx for DeviceNet,
during initial configuration of the system. In that case, graphical screens are
provided by the programmer to simplify configuration. However, some systems,
like the 1769-ADN DeviceNet adapter, also allow the bits to be altered as part of
the control program, using communication rungs. In that case, it is necessary to
understand the bit arrangement. Refer to the Compact Analog I/O User Manual,
publication number

1769-UM002

for additional details.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

CL
L7

CL
H7

CL
L6

CL
H6

CL
L5

CL
H5

CL
L4

CL
H4

CL
L3

CL
H3

CL
L2

CL
H2

CL
L1

CL
H1

CL
L0

CL
H0

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Real Time Sample Value

1

ERTS Reserved

2

EC

Reserved

EA

AL

EI

Reserved

Input Filter Sel Chl0

3

Reserved

Inpt Dta Fm
Chl0

Reserved

Inpt Tp/RngeSel Chl0

4

S

Process Alarm High Data Value Channel 0

5

S

Process Alarm Low Data Value Channel 0

6

S

Alarm Dead Band Value Channel 0

7

Pad

8

EC

Reserved

EA

AL

EI

Reserved

Inpt Filter Sel Chl1

9

Reserved

Inpt Dta Fm
Chl1

Reserved

Inpt Tp/RngeSel Chl1

10

S

Process Alarm High Data Value Channel 1

11

S

Process Alarm Low Data Value Channel 1