Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
145
I/O Memory Mapping Chapter 3
The bits are defined as follows:
• E = Channel Enable: (0 = Disabled, 1 = output 0 and hold Enabled,
process changes)
• Reserved = Set to zero
• SIU = System interrupt low clamp, under-range alarms: (0 = Disabled,
1 = Enabled)
• SIO = System interrupt high clamp, over-range alarms: (0 = Disabled,
1 = Enabled)
• LA = Latch low/high clamp, under/over-range alarms: (0 = Disabled,
1 = Enabled)
• ER = Enable ramping: (0 = Disabled, 1 = Enabled. Ramp rate limited by
fault states.)
• FM = Fault mode: (0 = Hold Last State, 1 = User Defined Value)
• PM = Program mode: (0 = Hold Last State, 1 = User Defined Value)
• HI = Hold for initialization: (0 = Disabled, 1 = Enabled)
• PFE = Program/idle to fault enable: (0 = Disabled, 1 = Enabled)
21
Channel 2 High Clamp
45
Channel 5 High Clamp
22
Channel 2 Ramp Rate
46
Channel 5 Ramp Rate
23
Channel 2 Spare
47
Channel 5 Spare
Word
Description
Word
Description
48
Channel 6 Configuration Word 0
56
Channel 7 Configuration Word 0
49
Channel 6 Configuration Word 1
57
Channel 7 Configuration Word 1
50
Channel 6 Fault Value Word
58
Channel 7 Fault Value Word
51
Channel 6 Program Idle Mode Word
59
Channel 7 Program Idle Mode Word
52
Channel 6 Low Clamp
60
Channel 7 Low Clamp
53
Channel 6 High Clamp
61
Channel 7 High Clamp
54
Channel 6 Ramp Rate
62
Channel 7 Ramp Rate
55
Channel 6 Spare
63
Channel 7 Spare
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
E
Reserved
SIU
SIO
LA
ER
FM
PM
HI
PFE
1
Reserved
Output Data
Format Select
Reserved
Output Type/
Range
Word
Description
Word
Description