Page 164: Module default condition

background image

164

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011

Chapter 3 I/O Memory Mapping

Fault State Word

Word 3, the fault state word, selects the hold last state or user-defined safe state
condition for each individual output on a system transition from Run to Fault.

Fault Value Word

(1)

The fault value word, word 4, is used to program the fault state value (0 = Off,
1 = On). Each output is individually configurable for on or off.

Program to Fault Enable Bit (PFE)

Word 0, bit 0, allows the selection of which data value, the program or fault value,
to apply to the output if a system in Program mode undergoes a system fault,
resulting in a change to the Fault mode.

Module Default Condition

(1)

The modules default condition is all zeros.

Condition Bit

Setting

User-defined Safe State

0

Hold Last State

1

Value

Bit Setting

Off

0

On

1

Value Applied

Bit Setting

Program

0

Fault

1

(1) TTL outputs are inverted (On = 1 = logic low voltage = 0…0.4V dc; Off = 0 = logic high voltage = 4.5…5.5V dc).

Use a NOT instruction in the ladder program to convert to traditional True = High logic.

Word or Bit Affected

Condition Applied

Word 0, Bit 0

Program-to-fault Enable

Program Value

Word 1

Program State

User-defined Safe State

Word 2

Program Value

Off

Word 3

Fault State

User-defined Safe State

Word 4

Fault Value

Off