Fault state word, Fault value wo rd, Program to fault enable bit (pfe) – Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 164: Module default condition
![background image](/manuals/579739/164/background.png)
164
Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 3 I/O Memory Mapping
Fault State Word
Word 3, the fault state word, selects the hold last state or user-defined safe state
condition for each individual output on a system transition from Run to Fault.
Fault Value Word
(1)
The fault value word, word 4, is used to program the fault state value (0 = Off,
1 = On). Each output is individually configurable for on or off.
Program to Fault Enable Bit (PFE)
Word 0, bit 0, allows the selection of which data value, the program or fault value,
to apply to the output if a system in Program mode undergoes a system fault,
resulting in a change to the Fault mode.
Module Default Condition
(1)
The modules default condition is all zeros.
Condition Bit
Setting
User-defined Safe State
0
Hold Last State
1
Value
Bit Setting
Off
0
On
1
Value Applied
Bit Setting
Program
0
Fault
1
(1) TTL outputs are inverted (On = 1 = logic low voltage = 0…0.4V dc; Off = 0 = logic high voltage = 4.5…5.5V dc).
Use a NOT instruction in the ladder program to convert to traditional True = High logic.
Word or Bit Affected
Condition Applied
Word 0, Bit 0
Program-to-fault Enable
Program Value
Word 1
Program State
User-defined Safe State
Word 2
Program Value
Off
Word 3
Fault State
User-defined Safe State
Word 4
Fault Value
Off