Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 68

68
Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 3 I/O Memory Mapping
The bits are defined as follows:
• SGN = Sign bit in 2’s complement format.
• Real Time Sample Value = Provides the ability to configure the Real Time
Sample Rate.
• ETS = Enable Time Stamping.
• EC = Enable Channel.
• EA = Enable Alarm.
• AL = Alarm Latch.
• EI = Enable Input Process Alarm Interrupt.
• Input Filter Sel ChIx = Input Channel Filter Setting.
• Inpt Dta Fm ChIx = Input Data Format Select.
• Inpt Tp/Rnge Sel ChIx = Input Type/Range Select.
• Process Alarm High Data Value Channel x = Provides the ability to
configure the Input Process Alarm High Value.
• Process Alarm Low Data Value Channel x = Provides the ability to
configure the Input Process Alarm Low Value.
• Alarm Dead Band Value Channel x = Provides the ability to configure the
Input Process Dead Band Value.
• Reserved = Bits not used, must be set to 0.
• EHI = Enable Output Channel Interrupt on High Clamp Alarm.
• ELI = Enable Output Channel Interrupt on Low Clamp Alarm.
• LC = Latch Low/High Clamp and Under/Over Range Alarm.
• ER = Enable Ramping.
• FM = Enable Fault Alternate Output State mode.
• PM = Enable Program/Idle Alternate Output State mode.
• PFE = Enable Program/Idle to Fault Alternate Output State mode.
• Outpt Fm ChIx = Output Data Format Select.
• Outpt Tp/Rnge Sel ChIx = Output Type/Range Select.
• Ramp Rate Channel x = Provides the ability to configure the Ramp Rate.
39
SGN
Clamp Low Data Value Channel 1
0
0
40
SGN
Ramp Rate Channel 1
0
0
41
Reserved
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0