beautypg.com

Rockwell Automation 1769-XXXX Compact I/O Modules  User Manual

Page 121

background image

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011

121

I/O Memory Mapping Chapter 3

Program Value Word

The program value word, word 2, is used to program the user-defined safe state
condition. Each output is individually configurable for on or off.

Fault State Word

Word 3, the fault state word, selects the hold last state or user-defined safe state
condition on a system transition from Run to Fault.

Fault Value Word

The fault value word, word 4, is used to program the fault state condition. Each
output is individually configurable for on or off.

Program to Fault Enable Bit (PFE)

Word 0, bit 0, allows the selection of which data value, the program or fault value,
to apply to the output if a system in Program mode undergoes a system fault,
resulting a change to Fault mode.

Condition

Bit Setting

Off

0

On

1

Condition Bit

Setting

User-defined Safe State

0

Hold Last State

1

Condition

Bit Setting

Off

0

On

1

Value Applied

Bit Setting

Program

0

Fault

1