beautypg.com

Rockwell Automation 1769-XXXX Compact I/O Modules  User Manual

Page 69

background image

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011

69

I/O Memory Mapping Chapter 3

Define

To
Select

Make these bit settings

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Input Filter
Selection /
-3 dB
Frequency

60 Hz

0

0

0

0

50 Hz

0

0

0

1

5 Hz

0

0

1

0

10 Hz

0

0

1

1

100 Hz

0

1

0

0

250 Hz

0

1

0

1

500 Hz

0

1

1

0

1000 Hz

0

1

1

1

No
Filter

1

0

0

0

Define

To Select

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Input
Type /
Range
Select

-10 to +10V dc

0

0

0

0

0 to 5V dc

0

0

0

1

0 to 10V dc

0

0

1

0

4 to 20 mA

0

0

1

1

1 to 5V dc

0

1

0

0

0 to 20 mA

0

1

0

1

Input
Data
Format
Select

Raw/
Proportional
Counts

0

0

0

Engineering
Units

0

0

1

Scaled for PID

0

1

0

Percent Range

0

1

1

Define

To Select

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Output
Type /
Range
Select

-10 to +10V dc

0

0

0

0

0 to 5V dc

0

0

0

1

0 to 10V dc

0

0

1

0

4 to 20 mA

0

0

1

1

1 to 5V dc

0

1

0

0

0 to 20 mA

0

1

0

1

Output
Data
Format
Select

Raw/
Proportional
Counts

0

0

0

Engineering
Units

0

0

1

Scaled for
PID

0

1

0

Percent
Range

0

1

1