beautypg.com

Din rail mounting, Din rail – Rockwell Automation 1769-XXXX Compact I/O Modules  User Manual

Page 16

background image

16

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011

Chapter 1 Install a 1769 Module

Panel Mounting Using the Dimensional Template

Panel Mounting Procedure Using Modules as a Template

The following procedure lets you use the assembled modules as a template for
drilling holes in the panel. If you have sophisticated panel mounting equipment,
you can use the dimensional template provided on

page 16

. Due to module

mounting hole tolerance, it is important to follow these procedures.

1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all

module-mounting holes on the panel.

3. Return the assembled modules to the clean work surface, including any

previously mounted modules.

4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.

7. Repeat steps 1…6 for any remaining modules.

DIN Rail Mounting

The module can be mounted using the following DIN rails:

• 35 x 7.5 mm (1.38 x 0.30 in.; EN 50 022 - 35 x 7.5)
• 35 x 15 mm (1.38 x 0.59 in.; EN 50 022 - 35 x 15)

Before mounting the module on a DIN rail, close the DIN rail latches. Press the
DIN rail mounting area of the module against the DIN rail. The latches will
momentarily open and lock into place.

Spacing for single-wide modules 35mm (1.378 in.)

Spacing for one-and-a half-wide modules 52.5mm (2.067 in.)

Refer to host controller documentation for this dimension.

Host Controller

Note: Overall hole spacing
tolerance:

±

0.4mm (0.016 in.).

30535-M

Ho

st Con

tro

lle

r

Note: Overall hole spacing
tolerance: +/- 0.4mm (0.016 in.).

Spacing for one-and-a half-wide modules 52.5mm (2.067 in.)

Refer to host controller documentation for this dimension.

Spacing for single-wide modules 35mm (1.378 in.)

TIP

If you are mounting more modules, mount only the last one of this group
and put the others aside. This reduces remounting time during drilling