background image

190

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011

Chapter 3 I/O Memory Mapping

• EI_Ox: Enable output interrupt; 1 = interrupt enabled, 0 = interrupt

disabled.

• IT_Ox: Output interrupt type. See page

191

.

• Operand_A_x: BOOLEAN operand A. See page

191

.

• Operand_B_x: BOOLEAN operand B. See page

191

.

• Operand_C_x: BOOLEAN operand C. See page

191

.

• Operator_1_x: BOOLEAN operator 1. See page

193

.

• Operator_2_x: BOOLEAN operator 2. See page

193

.

• Output delay x: Delay time from BOOLEAN expression transition from

false to true until output directed to transition from off to on. See page

194

.

• Output duration x: Pre-determined output pulse duration time. Time

from output directed to transition from off to on until output directed to
transition from on to off. See page

195

.

Wo

rd

Bit Position

(1)

(1) Darker shaded bit positions must be set to 0.

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0

Input
Filter

8 ms

0

0

0

0 s

0

0

1

100 µs

0

1

0

200 µs

0

1

1

500 µs

1

0

0

1 ms

1

0

1

2 ms

1

1

0

4 ms

1

1

1