I/O Memory Mapping Chapter 3

The bits are defined as follows:

• SGN = Sign bit in 2’s complement format.
• Nu = Not Used. Bit set to 0.
• Sx = General Status bit for input channels 0…15.
• Ox = Over range flag bits for input channels 0…15.
• Ux = Under range flag bits for input channels 0…15.
• Hx = High Alarm flag bits for input channels 0…15.
• Lx = Low Alarm flag bits for input channels 0…15.

Output Data File

For each module, slot

x, words 0 and 1 in the output data file contain the cancel

latched channel alarm control bits.

The bits are defined as follows:

• CLHx = Cancel High Process Alarm Latch for Input x. Allows each input

high-process-alarm latch to be individually cancelled. Cancel = 1.

• CLLx = Cancel Low Process Alarm Latch for Input x. Allows each input

low-process-alarm latch to be individually cancelled. Cancel = 1.

17

S15

S
14

S
13

S
12

S
11

S
10

S9

S8

S7

S6

S5

S4

S3

S2

S1

S0

18

L3

H3

U3

O3

L2

H2

U2

O2

L1

H1

U1

O1

L0

H0

U0

O0

19

L7

H7

U7

O7

L6

H6

U6

O6

L5

H5

U5

O5

L4

H4

U4

O4

20

L11

H
11

U
11

O
11

L
10

H
10

U
10

O
10

L9

H9

U9

O9

L8

H8

U8

O8

21

L15

H
15

U
15

O
15

L
14

H
14

U
14

O
14

L
13

H
13

U
13

O
13

L
12

H
12

U
12

O
12

Wo

rd

Bit Position

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

0

CLL
7

CLH
7

CLL
6

CLH
6

CLL
5

CLH
5

CLL
4

CLH
4

CLL
3

CLH
3

CLL
2

CLH
2

CLL
1

CLH
1

CLL
0

CLH
0

1

CLL
15

CLH
15

CLL
14

CLH
14

CLL
13

CLH
13

CLL
12

CLH
12

CLL
11

CLH
11

CLL
10

CLH
10

CLL
9

CLH
9

CLL
8

CLH
8

Wo

rd

Bit Position

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00