1769-ow16, Output module’s input data file, Program to fault enable bit (pfe) – Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 176: Module default condition
176
Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
Chapter 3 I/O Memory Mapping
Program to Fault Enable Bit (PFE)
Word 0, bit 0, allows the selection of which data value, the program or fault value,
to apply to the output if a system in Program mode undergoes a system fault,
resulting a change to Fault mode.
Module Default Condition
The modules default condition is all zeros, programming the conditions shown
below.
1769-OW16
The following I/O memory mapping lets you configure the 1769-OW16
module.
Output Module’s Input Data File
For each module, slot
x, input data file word 0 contains the state of the module’s
output data (output data echo) file word 0. During normal operation, these input
bits represent the logic state that the outputs are directed to by the control
program. They are also dependent upon these configurations:
• Program Mode configuration, if supported by the controller
• Fault Mode configuration, if supported by the controller
Value Applied
Bit Setting
Program
0
Fault
1
Word or Bit Affected
Condition Applied
Word 0, Bit 0:
Program-to-Fault Enable
Program Value
Word 1:
Program State
User-defined Safe State
Word 2:
Program Value
Off
Word 3:
Fault State
User-defined Safe State
Word 4:
Fault Value
Off
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
r
(1)
(1) r = read.
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r