Chapter 3 I/O Memory Mapping

Program to Fault Enable Bit (PFE)

Word 0, bit 0, allows the selection of which data value, the program or fault value,
to apply to the output if a system in Program mode undergoes a system fault,
resulting a change to Fault mode.

Module Default Condition

The modules default condition is all zeros, programming the conditions shown
below.

1769-OW16

The following I/O memory mapping lets you configure the 1769-OW16
module.

Output Module’s Input Data File

For each module, slot

x, input data file word 0 contains the state of the module’s

output data (output data echo) file word 0. During normal operation, these input
bits represent the logic state that the outputs are directed to by the control
program. They are also dependent upon these configurations:

• Program Mode configuration, if supported by the controller
• Fault Mode configuration, if supported by the controller

Value Applied

Bit Setting

Program

0

Fault

1

Word or Bit Affected

Condition Applied

Word 0, Bit 0:

Program-to-Fault Enable

Program Value

Word 1:

Program State

User-defined Safe State

Word 2:

Program Value

Off

Word 3:

Fault State

User-defined Safe State

Word 4:

Fault Value

Off

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

r

(1)

(1) r = read.

r

r

r

r

r

r

r

r

r

r

r

r

r

r

r