beautypg.com

1769-of4ci, Input data file – Rockwell Automation 1769-XXXX Compact I/O Modules  User Manual

Page 135

background image

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011

135

I/O Memory Mapping Chapter 3

1769-OF4CI

The following I/O memory mapping lets you configure the 1769-OF4CI
module.

Input Data File

For each module, slot

x, input data file words 2…5 contain the state of the

module’s output data (output data echo) file words 0…3. During normal
operation, these input words represent the analog values that the outputs are
directed to by the control program.

Define

To Select

Make these bit settings

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

Type /
Range
Select

-10…+10V
DC

0

0

0

0

0…5V DC

0

0

0

1

0…10V DC

0

0

1

0

4…20 mA

0

0

1

1

1…5V DC

0

1

0

0

0…20 mA

0

1

0

1

Data
Format
Select

Raw/
Proportional
Counts

0

0

0

Engineering
Units

0

0

1

Scaled for
PID

0

1

0

Percent
Range

0

1

1

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

S3

S2

S1

S0

1

H3

U3

O3

H2

U2

O2

H1

U1

O1

H0

U0

O0

2

Channel 0 Data Value

3

Channel 1 Data Value

4

Channel 2 Data Value

5

Channel 3 Data Value