Remove the terminal block, Wire the terminal block, Remove the terminal block wire the terminal block – Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 19

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
19
Install a 1769 Module Chapter 1
Remove the Terminal Block
To remove the terminal block, loosen the upper and lower retaining screws. The
terminal block will back away from the module as you remove the screws. When
replacing the terminal block, torque the retaining screws to 0.46 N
•
m (4.1 lb•in).
Wire the Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate.
You can use the bare wire or a spade lug. The terminals will accept a 6.35
mm (0.25 in.) spade lug.
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 N•m
(6 lb•in).
Item
Description
1
Wiring the finger-safe terminal block
2
Lower retaining screws
3
Upper retaining screws
TIP
The terminal screws are non-captive. You can use a ring lug [maximum
6.35 mm (0.25 in.) o.d. with a 3.53 mm (0.139 in.) minimum i.d. (M3.5)]
with the module.
TIP
If you need to remove the finger-safe cover, insert a screwdriver into one
of the square wiring holes and gently pry the cover off. If you wire the
terminal block with the finger-safe cover removed, you will not be able to
put it back on the terminal block because the wires will be in the way.
1
3
2