1769-if4fxof2f, Input data file – Rockwell Automation 1769-XXXX Compact I/O Modules User Manual
Page 65

Rockwell Automation Publication 1769-IN088A-EN-P - February 2011
65
I/O Memory Mapping Chapter 3
1769-IF4FXOF2F
The following I/O memory mapping lets you configure the 1769-IF4FXOF2F
module.
Input Data File
For each module, slot
x, words 0…3 in the input data file contain the converted
value of the module’s analog input channels. Word 4 in the input data file
contains the time stamp value corresponding to the module's last input data
sampling period. Words 5 and 6 in the input data file contain status bits for the
analog input channels. Word 7 in the input data file contains status bits for the
analog output channels. Words 8 to 9 contain the directed values of the analog
output channels (output data echo).
The bits are defined as follows:
• SGN = Sign bit in 2’s complement format.
• Nu = Not Used. Bit set to 0.
• SIx = General Status bit for input channels 0…3.
• OIx = Over range flag bits for input channels 0…3.
• UIx = Under range flag bits for input channels 0…3.
• HIx = High Alarm flag bits for input channels 0…3.
• LIx = Low Alarm flag bits for input channels 0…3.
• SOx = General Status bit for output channels 0…1.
• OOx = Over range flag bits for output channels 0…1.
• UOx = Under range flag bits for output channels 0…1.
Wo
rd
Bit Position
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
0
SGN Analog Read (Input) Data Value Channel 0
0
1
SGN Analog Read (Input) Data Value Channel 1
0
2
SGN Analog Read (Input) Data Value Channel 2
0
3
SGN Analog Read (Input) Data Value Channel 3
0
4
0
Time Stamp Value
5
Nu
Nu
Nu
Nu
Nu Nu
Nu
Nu
Nu
Nu
Nu
Nu
SI3
SI2
SI1
SI0
6
LI3
HI3
UI3
OI3 LI2 HI2
UI2
OI2
LI1
HI1
UI1
OI1
LI0
HI0
UI0
OI0
7
Nu
Nu
UO1 OO1 Nu Nu
UO0 OO0 Nu
Nu
Nu
Nu
Nu
Nu
SO1 SO0
8
SGN Output Data Loopback/Echo Channel 0
0
0
9
SGN Output Data Loopback/Echo Channel 1
0
0