ControlNet I/O MapĆEntry Status Words

Appendix D

and Error Messages

D-4

Possible Corrective Action(s)

Explanation / Possible Cause(s)

Error Message

Hex.

Code

Decimal

Code

65527

0xFFF7

MODULE

TIMED

OUT

The node or slot contains the wrong

module type

Insert the proper module in the correct slot of

the target node

An incorrect module type was

entered in the map table

Enter the correct module type in the mapĆ

table entry

65529

0xFFF9

COMM

ERROR

CAUSED

LOSS

OF

DATA

A communication error between the

module and adapter caused data to

Make sure that the proper module is properly

seated in the correct slot of the target node

odu e a d adap e caused da a o

be lost

Make sure that the correct module type is

entered in the mapĆtable entry

65530

0xFFFA

MODULE

DECLARED

INVALID

LENGTH

The node or slot contains the wrong

module type

Insert the proper module in the correct slot of

the target node

An incorrect module type was

entered in the map table

Enter the correct module type in the mapĆ

table entry

65531

0xFFFB

READ

DATA

INVALID

The node or slot contains the wrong

module type

Insert the proper module in the correct slot of

the target node

An incorrect module type was

entered in the map table

Enter the correct module type in the mapĆ

table entry

65532

0xFFFC

WRITE

DATA

INVALID

The node or slot contains the wrong

module type

Insert the proper module in the correct slot of

the target node

An incorrect module type was

entered in the map table

Enter the correct module type in the

mapĆtable entry

65533

0xFFFD

DATA

TABLE

TOO

SMALL

The processor data table is too

small

Increase the size of the data table to

accommodate the transfer length