Chapter 5 – Rockwell Automation 1785-L20C_L40C, D17856.5.14 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 75

Chapter 5
Monitoring and Troubleshooting Your
ControlNet System
5-13
This status field:
Word;
Bits:
①
Displays:
②
COUNTERS
LOCKED
when the display of the counters stops changingĊthe counters continue to run in the background;
current values are continuously updated when COUNTERS
LOCKED is not displayed
media
usage
the media redundancy characteristic for the ControlNet channelĊ
A/B
,
A
Only
, or
B
Only
Frames
transmitted
good
6; 15Ć08
number of good frames transmitted
transmitted
good
6; 15Ć08
5; 07Ć00
5; 15Ć08
number of good frames transmitted
transmitted
aborted
received good
5; 15 08
9; 07Ć00
7; 07Ć00
number of frames that could not be transmitted completely and were aborted during transmission
number of good frames received on the active channel
received
good
7; 07Ć00
7; 15Ć08
6; 07Ć00
number of good frames received on the active channel
received
aborted
received bad
6; 07 00
12; 07Ć00
8; 15Ć08
number of frames received that were aborted during transmission on the active channel
number of unusable frames received on the active channel
received
bad
total
received
8; 15Ć08
number of unusable frames received on the active channel
number of framesĊgood and badĊreceived on the active channel
channel
A
errors
8; 07Ć00
number of frames received on channel A that were unusable independent of the active
channelĊchannel selected for reception
channel
B
errors
9; 15Ć08
number of frames received on channel B that were unusable independent of the active
channelĊchannel selected for reception
channel
warnings
23; 07Ć06
any channel that is receiving a low level of unusable framesĊi.e., frames containing data errors
Network
Capacity
update
time
overload
10; 07Ć00
number of times that a NUI passes with no opportunity to transmit
update
time
overload
blockage
10; 07Ć00
11; 07Ć00
number of times that a NUI passes with no opportunity to transmit
number of times that a NUI does not contain enough room to allow the transmission of a particular
frame
moderator
node
15; 15Ć08
frame
network address of the node that is transmitting the moderator frameĊalways the lowest active
network address
mismatch
events
16; 15Ć08
network address
number of times a moderator frame was received with network parameters different from those
in the receiving node
unheard
occurrences
16; 07Ć00
in the receiving node
number of times a node can receive a frame from a lower network address but cannot receive
a moderator
Misc
out
of
step
events
10; 15Ć08
number of times any event prevents a frame from being transmitted in the NUI in which it should be
t
itt d
network
silent
13; 15Ć08
y
p
g
transmitted
number of times a node cannot hear any network activity for three consecutive NUIs
number of times that a start of frame could not be detected
noise
detected
commands
received
14; 15Ć08
17; 15Ć08
number of times that a start of frame could not be detected
number of station commands received directly from the network that bypass the node's host
processor
commands
received
collisions
17; 15Ć08
14; 07Ć00
processor
number of times that a node prevents the transmission of a frame because it would cause a
collision to occur
①
In userĆspecified Diagnostics File
②
All counters display only the status of the node being examined