Chapter 5

Monitoring and Troubleshooting Your

ControlNet System

5-7

Using the ControlNet I/O Mapping (Monitor) Screen

Follow the steps on the left to go to the ControlNet I/O Mapping
(Monitor) screen.

ControlNet – I/O Mapping MONITOR

Channel 2 Configuration NODE 1

Status File: N32 Network Update Time(ms): 5 Sch BW(%): 64

Data Input File: N34 –––––– Processor’s ControlNet Resource Usage –––––

Data Output File: N36 Map Entries PLC BW (%) DIF (%) DOF (%)

Dflt Config File: N38 8 8 10 8

Node Mod/Msg Type Act Net Pckt Input Output Status Config

S/M Time(ms) File Size File Size Offset File Size

1 PLC–5/40C n/a n/a n/a n/a n/a n/a n/a

1 Peer Out to 3 20 n/a n/a N36:0 64 0 n/a n/a

2 1771–ACN 5 I:010 8 O:010 8 3 n/a n/a

6 1771–IFE/A 10 N34:0 20 n/a n/a 6 N38:0 37

7 1771–OFE/A 10 N34:20 5 N36:64 5 9 N36:64 13

3 PLC–5/20C n/a n/a n/a n/a n/a n/a n/a

1 Peer In 5 N34:25 24 n/a n/a 15 n/a n/a

Press a function key, page up or page down, or enter a node.s/m number.

>

Rem Prog Forces:None Display:Slot/Message 5/40C File CN

Map Select Node View Monitor Define I/O Monitor

Edit Display Monitor Times Status LclRack Monitor Actions

F2 F3 F4 F5 F6 F7 F8 F9

If you want to:

Do this:

quickly position the cursor on a specific entry in the list

1. Type the node number, a period (.),

and the slot or message number of

the entryĊe.g.,

2.7

2. Press

[Enter]

go to the ControlNet I/O Mapping (Edit) screen

Press

[F2]—Map

Edit

select the display of slots, messages, or slots and messages in

the list

1. Press

[F3]—Select

Display

2. Press

[F2]—Slot

Display

or

[F3]—Message

Display

or

[F4]—Slot/Message

go to the ControlNet Node Information (Monitor) screen

Press

[F4]—Node

Monitor

view the Actual Network Packet Time (ANPT) and Expected

Network Packet Time (ENPT) instead of the input, output,

status, and configuration information

Press

[F5]—View

Times

go to the ControlNet Map Entries Status screen

Press

[F6]—Monitor

Status

define the characteristics of the local chassis
Important: This option is not available if you are

programming online.

Press

[F7]—Define

LclRack

go to the I/O Configuration Monitor Utility

1. Move your cursor to an analog entry
2. Press

[F8]—I/O

Monitor

go to the ControlNet I/O Action (Monitor) screen
Important: This option is not available if the display mode is

set to

Message

Display

on this screen or the ControlNet

View Times screen by using

[F3]—Select

Display

.

1. Move the cursor to the 1794 I/O

module entry who's actions you want

to monitor

2. Press

[F9]—Monitor

Actions

return to the ControlNet Node Information (Monitor) screen

Press

[Esc]

Channel

Overview

Channel

Configuration

6200

Main Menu

General

Utility

F3

Online

Program

Offline

Program

F1

F7

or

F4

F5

(Monitor)

Map

Monitor

F2

Move cursor to

Channel 2: CONTROLNET