Using the controlnet i/o mapping (monitor) screen, Chapter 5 – Rockwell Automation 1785-L20C_L40C, D17856.5.14 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 69

Chapter 5
Monitoring and Troubleshooting Your
ControlNet System
5-7
Using the ControlNet I/O Mapping (Monitor) Screen
Follow the steps on the left to go to the ControlNet I/O Mapping
(Monitor) screen.
ControlNet – I/O Mapping MONITOR
Channel 2 Configuration NODE 1
Status File: N32 Network Update Time(ms): 5 Sch BW(%): 64
Data Input File: N34 –––––– Processor’s ControlNet Resource Usage –––––
Data Output File: N36 Map Entries PLC BW (%) DIF (%) DOF (%)
Dflt Config File: N38 8 8 10 8
Node Mod/Msg Type Act Net Pckt Input Output Status Config
S/M Time(ms) File Size File Size Offset File Size
1 PLC–5/40C n/a n/a n/a n/a n/a n/a n/a
1 Peer Out to 3 20 n/a n/a N36:0 64 0 n/a n/a
2 1771–ACN 5 I:010 8 O:010 8 3 n/a n/a
6 1771–IFE/A 10 N34:0 20 n/a n/a 6 N38:0 37
7 1771–OFE/A 10 N34:20 5 N36:64 5 9 N36:64 13
3 PLC–5/20C n/a n/a n/a n/a n/a n/a n/a
1 Peer In 5 N34:25 24 n/a n/a 15 n/a n/a
Press a function key, page up or page down, or enter a node.s/m number.
>
Rem Prog Forces:None Display:Slot/Message 5/40C File CN
Map Select Node View Monitor Define I/O Monitor
Edit Display Monitor Times Status LclRack Monitor Actions
F2 F3 F4 F5 F6 F7 F8 F9
If you want to:
Do this:
quickly position the cursor on a specific entry in the list
1. Type the node number, a period (.),
and the slot or message number of
the entryĊe.g.,
2.7
2. Press
[Enter]
go to the ControlNet I/O Mapping (Edit) screen
Press
[F2]—Map
Edit
select the display of slots, messages, or slots and messages in
the list
1. Press
[F3]—Select
Display
2. Press
[F2]—Slot
Display
or
[F3]—Message
Display
or
[F4]—Slot/Message
go to the ControlNet Node Information (Monitor) screen
Press
[F4]—Node
Monitor
view the Actual Network Packet Time (ANPT) and Expected
Network Packet Time (ENPT) instead of the input, output,
status, and configuration information
Press
[F5]—View
Times
go to the ControlNet Map Entries Status screen
Press
[F6]—Monitor
Status
define the characteristics of the local chassis
Important: This option is not available if you are
programming online.
Press
[F7]—Define
LclRack
go to the I/O Configuration Monitor Utility
1. Move your cursor to an analog entry
2. Press
[F8]—I/O
Monitor
go to the ControlNet I/O Action (Monitor) screen
Important: This option is not available if the display mode is
set to
Message
Display
on this screen or the ControlNet
View Times screen by using
[F3]—Select
Display
.
1. Move the cursor to the 1794 I/O
module entry who's actions you want
to monitor
2. Press
[F9]—Monitor
Actions
return to the ControlNet Node Information (Monitor) screen
Press
[Esc]
Channel
Overview
Channel
Configuration
6200
Main Menu
General
Utility
F3
Online
Program
Offline
Program
F1
F7
or
F4
F5
(Monitor)
Map
Monitor
F2
Move cursor to
Channel 2: CONTROLNET