Configuring Your ControlNet System
3-10
Editing ControlNet 1794 I/O Module Action
Follow the steps on the left to the ControlNet I/O Action (Edit) screen.
Important: Only one user on a network can enter a processor’s
ControlNet 1794 I/O Module Action screen at one time.
ControlNet – I/O Action EDIT
Channel 2 Configuration NODE 1
Node 4 1794–ACN
Module Type Fault Action Idle Action Fault Action
Slot From Idle
0 1794–Digital Reset Reset Idle
1 1794–IE8/A Reset Reset Idle
2 1794–OE4/A Safe Reset Idle
3 1794–IE4XOE2/A Safe Reset Idle
4 1794–Digital Reset Reset Idle
5 1794–Digital Reset Reset Idle
6 1794–Digital Reset Reset Idle
7 1794–Digital Reset Reset Idle
Press a function key or cursor key.
>
Rem Prog Forces:None 5/40C File CN
Accept Map Toggle Toggle
Edits Edit All Entry
F1 F2 F8 F10
If you want to:
Do this:
change a system's fault action
Ċi.e., the action that it takes
when it faults
1. Move the cursor to the
Fault
Action
column
2. Press
[F8]—Toggle
All
to toggle between:
•
Reset
Ċto change all outputs to zero
•
Hold
Last
Ċto maintain all current output values
•
Safe
Ċto change all outputs to userĆspecified fail-safe values
change a system's idle action
Ċi.e., the action that it takes
when it becomes idle
1. Move the cursor to the
Idle
Action
column
2. Press
[F8]—Toggle
All
to toggle between:
•
Reset
Ċto change all outputs to zero
•
Hold
Last
Ċto maintain all current output values
•
Safe
Ċto change all outputs to userĆspecified fail-safe values
change a system's fault action
from idleĊi.e., the action that
it takes when it faults from idle
1. Move the cursor to the
Fault
Action
From
Idle
column
2. Press
[F8]—Toggle
All
to toggle between:
•
Idle
Ċto use the idle action
•
Fault
Ċto use the fault action
change a module's fault action
Ċi.e., the action that it takes
when it faults
1. Move the cursor to the module's field
Fault
Action
field
2. Press
[F10]—Toggle
Entry
to toggle between:
•
Reset
Ċto change all outputs to zero
•
Hold
Last
Ċto maintain all current output values
•
Safe
Ċto change all outputs to userĆspecified fail-safe values
Channel
Overview
Channel
Configuration
6200
Main Menu
General
Utility
F3
Online
Program
Offline
Program
F1
F7
or
F4
F5
(Monitor)
Map
Monitor
F2
Map
Edit
F2
Edit
Actions
F9
Move cursor to
Channel 2: CONTROLNET
Move cursor to
a 1794 I/O entry