Chapter 1

Installing Your ControlNet PLCĆ5 Processor

1-11

Specify RS-232C, RS-422A, or RS-423 communication for Channel 0 by
setting the switches of assembly SW2.

Front of

Processor

Front of

Processor

Bottom View of PLCĆ5/20C Processor

Switch Assembly SW2

Bottom View of PLCĆ5/40C processor

Switch Assembly SW2

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

To Specify:

Set Switches:

To Specify:

1

2

3

4

5

6

7

8

9

10

RSĆ232C

ON

ON

ON OFF OFF ON

ON OFF ON OFF

RSĆ422A

OFF OFF ON OFF OFF OFF OFF OFF ON OFF

RSĆ423

ON

ON

ON OFF OFF ON OFF OFF ON OFF

Select your processor’s ControlNet network address by setting the two
10-digit rotary switches on the top of the processor.

00

10

20

30

40

50

60

70

80

90

0

1

2

3

4

5

6

7

8

9

NET ADDRESS

Network address 01

is shown

You can select from as many as 99 network addresses (from 01 to 99) for a
processor on a ControlNet link. 00 is invalid.

Specifying the Serial

Interface of Channel 0

Toggle pushed

ON

Toggle pushed

OFF

toward BOTTOM

toward TOP

Selecting the ControlNet

Network Address of

Channel 2

Tip

For optimum throughput,

assign addresses to your

ControlNet nodes in a

sequential order starting

with 01 for the controlling

processor.