Chapter 2

Planning to Use Your ControlNet

PLCĆ5 Processor

2-8

Remote I/O

The following table shows the default number of input and output words
reserved by the 6200 PLC-5 Programming Software for the different sizes
and addressing modes of non-ControlNet remote I/O if you first configure
non-ControlNet remote I/O on your processor:

Addressing Mode

Number of Words Reserved

Addressing Mode

4 Slots

8 Slots

12 Slots

16 Slots

2 Slot

2

4

6

8

1 Slot

4

8

12

16

1/2 Slot

8

16

24

32

The 6200 PLC-5 Programming Software reserves non-ControlNet remote-
I/O output- and input-image space according to these guidelines:

It does not overlap processor-resident local I/O reserved image space

It addresses input- and output-image space offset in octal from

- 00-37—for the PLC-5/20C processor
- 00-177—for the PLC-5/40C processor

The output-image offset value in the I/O map corresponds to the first

slot of the referenced chassis—i.e., in a 4-slot chassis set for 1-slot
addressing, the corresponding output-image offset of O:10 would map
the words O:10, O:11, O:12, and O:13 to slots 0, 1, 2, and 3 respectively

The input-image offset corresponds to the first slot in the referenced

rack, and the offset location of the input modules in that rack
corresponds to the same offset in the image table—i.e., if a chassis set
for 1-slot addressing has an input-image offset of I:10 and an input
module in slot 3 (of 0-7), the word that corresponds to that input module
would be I:10 + 3, or I:13