S:11ćs:12 – Rockwell Automation 1785-L20C_L40C, D17856.5.14 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 84
Processor Status File
Appendix B
B-3
This word of
the status file:
Stores:
S:11
Major fault
Bit
Description
0
corrupted program file (codes 10Ć19)
1
corrupted address in ladder file (codes 10Ć29)
2
programming error (codes 30Ć49)
3
SFC fault (codes 71Ć79)
4
error while assembling program (code 70)
5
startĆup protection fault
6
peripheral device fault
7
jumped to fault routine (codes 0Ć9)
8
watchdog faulted
9
system configured wrong (codes 80Ć89)
10
recoverable hardware error
11
MCP does not exist or is not ladder or SFC file
12
PII does not exist or is not ladder
13
STI does not exist or is not ladder
14
fault routine does not exist or is not ladder
15
fault routine file is not a ladder file
S:12
Fault codes
Code
Description
0Ć9
userĆdefined
10
failed data table check
11
bad user program checksum
12
bad integer operand type
13
bad mixed mode operand type
14
not enough operands for instruction
15
too many operands for instruction
16
bad instruction found
17
no expression end
18
missing end of edit zone
19
download aborted
20
indirect address out of range (high)
21
indirect address out of range (low)
22
attempt to access undefined file
23
file number less than 0 or greater than number of defined files; or,
indirect reference to file 0, 1, 2; or bad file number
24
indirect reference to wrong file type
30
subroutine jump nesting level exceeded
31
too few subroutine parameters
32
jump to nonĆladder file
33
CAR routine not 68000 code
34
bad timer parameters entered
35
bad PID delta time entered
36
PID setpoint out of range
37
invalid I/O specified in an immediate I/O instruction
38
invalid use of return instruction
39
FOR loop missing NXT
40
control file too small
41
NXT instruction with no FOR
42
jump target does not exist
43
file is not an SFC
44
error using SFR
45
invalid channel number entered
46
IDI or IDO instruction length operand too long ( > 64 words)
47Ć69
reserved
S:11ĆS:12