Chapter 3

Configuring Your ControlNet System

3-11

Do this:

If you want to:

change a module's idle action

Ċi.e., the action that it takes

when it becomes idle

1. Move the cursor to the module's

Idle

Action

field

2. Press

[F10]—Toggle

Entry

to toggle between:

Reset

Ċto change all outputs to zero

Hold

Last

Ċto maintain all current output values

Safe

Ċto change all outputs to userĆspecified fail-safe values

change a module's fault action

from idleĊi.e., the action that

it takes when it faults from idle

1. Move the cursor to the module's

Fault

Action

From

Idle

field

2. Press

[F10]—Toggle

Entry

to toggle between:

Idle

Ċto use the idle action

Fault

Ċto use the fault action

apply pending edits and return

to the ControlNet I/O Mapping

(Edit) screen

Press

[F1]—Accept

Edits

go back to the ControlNet I/O

Mapping (Edit) screen

Press

[F2]—Map

Edit

or

[Esc]