S:12ćs:16 – Rockwell Automation 1785-L20C_L40C, D17856.5.14 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 85
Processor Status File
Appendix B
B-4
This word of
the status file:
Stores:
S:12
(continued)
Fault codes
Code
Description
70
duplicate labels
71
SFC subchart is already executing
72
tried to stop an SFC that is not running
73
maximum number of SFC subcharts exceeded
74
SFC file error
75
SFC contains too many active steps
77
SFC references a step, transition, subchart, or SC file that is
missing, empty, or too small
78
SFC could not continue after power loss
79
error in downloading an SFC to a processor that cannot run SFCs
or this specific PLC processor does not support this enhanced
SFC
80
I/O configuration error
81
illegal setting of I/O chassis backplane switch
82
illegal cartridge type
83
user watchdog fault
84
error in userĆconfigured adapter mode block transfers
85 bad
cartridge
86
cartridge incompatible with host
87
rack overlap (includes any adapter channel)
88
scanner channels are overloading the remote I/O buffer; too much
data for the processor to process
90
coprocessor extensive memory test failed
91
coprocessor undefined message type
92
coprocessor illegal pool index
93
coprocessor illegal maximum pool size
94
coprocessor illegal ASCII message
95
coprocessor reported fault
96
coprocessor present signal lost
97
coprocessor illegal minimum pool size
98
coprocessor first/last 16 bytes RAM test failed
99
coprocessor to processor data transfer faulted
100
processor to coprocessor transfer failed
101
coprocessor end of scan transfer failed
102
file number specified for raw data transfer through the coprocessor
is an illegal value
103
element number specified for raw data transfer through the
coprocessor is an illegal value
104
size of the transfer requested through the coprocessor is an
illegal size
105
offset into the raw transfer segment of the coprocessor is an
illegal value
106
coprocessor transfer protection violation
200
ControlNet output transfer missed
201
ControlNet input data missed
202
ControlNet diagnostic data missed
203
ControlNet scheduled transmit data overflow
204
ControlNet configuration too complex for the PLCĆ5 processor
S:13
Program file where fault occurred
S:14
Rung number where fault occurred
S:15
VME status file
S:16
I/O Status File
S:12ĆS:16