Installing Your ControlNet PLCĆ5 Processor

1-14

Use 1770-CD cable to connect the processor to a DH+ link.

Follow these guidelines while installing DH+ communication links:

do not exceed these cable lengths:

- trunk-cable length—3,048 m (approximately 10,000 cable-ft)
- drop-cable length—30.4 m (approximately 100 cable-ft)

do not connect more than 64 stations on a single DH+ link

19339

82

W

or

150

W resistor

Clear

Shield

Blue

Clear

Shield

Blue

82Ω

or

150

W

resistor

Use the 3Ćpin connector on the processor to

connect a DH+ link. The connector's port must be

configured to support a DH+ communication link.

You can install a DH+ link two ways:

trunk cable/drop cableĊfrom the drop cable to

the connector screw terminals on the DH+

connectors of the processor

daisy chainĊto the connector screw terminals

on the DH+ connectors of the processor

To make connections:

1. Connect the signal conductor with clear

insulation to the 3Ćpin connector terminal 1

at each end of each cable segment.

2. Connect the shield drain wire to the center

terminal of the 3Ćpin connector at both ends

of each cable segment.

3. Connect the signal conductor with blue

insulation to the 3Ćpin connector terminal 2

at each end of each cable segment.

PLCĆ5/40C

Processor

PLCĆ5/20C

Processor

More

For more information, see the Data Highway/Data

Highway Plus/Data Highway II/Data Highway 485

Cable Installation Manual, publication 1770Ć6.2.2.

Installing a DH+ Link