Chapter 1

Installing Your ControlNet PLCĆ5 Processor

1-9

Replacing the Battery

Replace the lithium battery every year or when the BATT status indicator
is red. For estimated battery lifetimes, see the table below:

Processor

Temperature

WorstĆCase BatteryĆLife Estimates

Power Off 100% Power Off 50%

Battery Duration

PLCĆ5/20C

60

°

C

218 days

1.17 years

3.7 days

25

°

C

1.7 years

3.34 years

15 days

PLCĆ5/40C

60

°

C

105 days

207 days

40 hours

25

°

C

1.3 years

2.57 years

10.8 days

The battery status indicator (BATT) warns you when the battery is low. These durations are

based on the battery supplying the only power to the processorĊpower to the chassis is

offĊonce the status indicator first lights.

Disposing of the Battery

Do not dispose of lithium batteries in a general trash collection when their
combined weight is greater than or equal to 0.5 gram. A single 1770-XYC
battery contains 0.65 grams of lithium. Check your state and local
regulations that deal with the disposal of lithium batteries.

ATTENTION: Follow these precautions:

Do not incinerate or expose the battery to
high temperatures.

Do not solder the battery or leads; the battery
could explode.

Do not open, puncture, or crush the battery. The
battery could explode or toxic, corrosive, and
flammable chemicals could be exposed.

Do not charge the battery. An explosion may result,
or the cell may overheat and cause burns.

Do not short positive and negative terminals together.
The battery will heat up.

Tip

You can insert or remove the

battery without powering down

the processor. If you do not

want to lose your program,

make sure that the processor

is powered when replacing

the battery.