Flt driv status, Fault alarms, Flt clear mode – Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 96: Ground warning, Faults

5–30
Programming
[Flt Driv Status]
This parameter stores and displays
the last [Drive Status] prior to a
fault.
Bits 0-7 are displayed on lower half
of line 2 on HIM display, while, bits
8-15 are displayed on the upper half
of line 2.
With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number
146
Parameter Type
Read Only
Enabled
Running
Command Direction
Actual Direction
Accelerating
Decelerating
Faulted
At Speed
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Alarm
0 = Reverse
1 = Forward
0 = Reverse
1 = Forward
Reference
ID
Local
Adapter ID
Reference
15 14 13 12
Freq Select 1
0
0
0
0
Preset Freq 1
0
0
0
1
Preset Freq 2
0
0
1
0
Preset Freq 3
0
0
1
1
Preset Freq 4
0
1
0
0
Preset Freq 5
0
1
0
1
Preset Freq 6
0
1
1
0
Preset Freq 7
0
1
1
1
Freq Select 2
1
0
0
0
Adapter 1
1
0
0
1
Adapter 2
1
0
1
0
Adapter 3
1
0
1
1
Adapter 4
1
1
0
0
Adapter 5
1
1
0
1
Adapter 6
1
1
1
0
Jog Frequency 1
1
1
1
Local
11 10 9
TB3
0
0
0
1
0
0
1
2
0
1
0
3
0
1
1
4
1
0
0
5
1
0
1
6
1
1
0
Unused
1
1
1
Bit 14
[Fault Alarms]
This parameter stores and displays
the last alarm conditions present
prior to a fault. Refer to Chapter 6
for further alarm information.
With a Series A (version 3.0) or
Series B HIM, a Status description
(bit ENUM) is displayed on line 1.
Parameter Number
173
Parameter Type
Read Only
Bus Charging
Regenerating Current Limit
Regenerating Voltage Limit
Line Loss In Progress
Motor Stalled
Ground Warning
Bit 15
Bit 13 Bit 12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Overcurrent
Sync Loss
Bit 14
Hardware Current Limit
Motoring Current Limit
Unused
Unused
Voltage Check
Heatsink Temp
Auxiliary Input
4-20 mA Loss
[Flt Clear Mode]
This parameter controls the method for clearing
faults.
Parameter Number
39
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
Faults cleared only by cycling power
“Enabled” 1
Faults cleared by issuing a valid
stop command or cycling power
[Ground Warning]
Enables the Ground Warning fault when the drive
senses ground current in excess of 2 amperes
(approximate). Refer to Chapter 6 for further
information.
Parameter Number
204
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
No Fault Generated
“Enabled” 1
Ground Warning Generated
Faults