Dc boost select, Full custom fixed fan select 1 & 2/no boost, Start boost – Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 79: Run boost

background image

5–13

Programming

[DC Boost Select]

This parameter sets the level of DC Boost that will
be applied at low frequencies (typically 0-7 Hz).
Auto settings automatically measure motor
resistance and adjust the boost voltage to maintain
constant boost performance regardless of changing
motor temperature. This setting represents the
amount of voltage required to produce the percent of
drive rated current in a non-rotating motor (i.e. 45%).

If this boost voltage (typically used for faster
acceleration) is excessive for constant low speed
operation, it can be automatically reduced to
acceptable levels by programming [Run/Accel
Boost].

Refer to the diagram below.

Parameter Number

9

Parameter Type

Read and Write

Factory Default

“Auto 30%”

Units

Display Drive

“Fan Sel #1” 0

see “Fan Select/No Boost” drawing.

“Fan Sel #2” 1

see “Fan Select/No Boost” drawing.

“No Boost” 2

see “Fan Select/No Boost” drawing.

“Auto 15%” 3

minimum auto boost

“Auto 30%” 4

.

“Auto 45%” 5

.

“Auto 60%” 6

.

“Auto 75%” 7

.

“Auto 90%” 8

.

“Auto 105%” 9

.

“Auto 120%” 10

maximum auto boost

“Full Custom” 11

see “Full Custom” drawing below

“Fixed” 12

see “Fixed” drawing below

Base

Voltage

0

0

Base Frequency

100%

50%

42%
35%

100%

50%

Fan 1

Fan 2

No Boost

Voltage

0

0

Frequency

Motor Rated

Maximum

Start Boost

Break Voltage
Break Frequency

Maximum

Base Voltage

Base Frequency

Maximum Voltage
Maximum Frequency

Motor Rated

Full Custom

Fixed

Fan Select 1 & 2/No Boost

Voltage

0

0

Frequency

Run Boost

Start Boost

B

A

Base Voltage

Base Frequency

[Start Boost]

This parameter sets the DC start boost level for
acceleration when [DC Boost Select] is set to “Fixed”
or “Full Custom.”

Parameter Number

48

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

9.5% of Drive Rated Voltage

[Run Boost]

This parameter sets the DC boost level for constant
speed level when [DC Boost Select] is set to “Fixed”.

Parameter Number

83

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

9.5% of Drive Rated Voltage

Advanced Setup