Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 101

5–35
Programming
[Heatsink Temp]
This parameter displays the heatsink temperature.
Parameter Number
70
Parameter Type
Read Only
Display Units / Drive Units
1
°
C / Deg. C
Factory Default
None
Minimum Value
0
Maximum Value
255
°
C
[Set Defaults]
Setting this parameter to “Defaults Init” resets all
parameters to their factory values.
This parameter cannot be changed while the drive is
running.
Parameter Number
64
Parameter Type
Read and Write
Factory Default
“Ready”
Units
Display Drive
“Ready” 0
Display after function complete.
“Store to EE” 1
Not implemented.
“Rcll frm EE” 2
Not implemented.
“Default Init” 3
Resets all parameters to factory
settings.
[Application Sts]
The value of this parameter provides a checksum
value that indicates a change in drive programming
has occurred.
With a Series A (version 3.0) or Series B HIM, a
Status description (bit ENUM) is displayed on line 1.
Parameter Number
200
Parameter Type
Read Only
Factory Default
00000000
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Sync Input – 0 = Disabled, 1 = Enabled
P Jump – 0 = Disabled, 1 = Enabled
Unused
[DC Bus Memory]
This parameter displays the nominal DC bus voltage
level. This value is used to determine line loss,
overvoltage, decel frequency and other points.
Parameter Number
212
Parameter Type
Read Only
Display Units / Drive Units
1 Volt / Volts
Display
Volts
Diagnostics