Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 78

5–12
Programming
This group contains parameters that are required to setup advanced functions of the drive
for complex applications.
Advanced
Setup
[Minimum Freq]
This parameter sets the lowest frequency the drive
will output.
Parameter Number
16
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Hertz / Hertz x 10
Factory Default
0.0 Hz
Minimum Value
0.0 Hz
Maximum Value
120.0 Hz
[Maximum Freq]
This parameter sets the highest frequency the drive
will output.
This parameter cannot be changed while the drive is
running.
Parameter Number
19
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Hertz / Hertz x 10
Factory Default
60.0 Hz
Minimum Value
25.0 Hz
Maximum Value
400.0 Hz
[Base Frequency]
This value should be set to the motor nameplate
rated frequency.
Parameter Number
17
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Hertz / Hertz x 10
Factory Default
60.0 Hz
Minimum Value
25.0 Hz
Maximum Value
400.0 Hz
[Base Voltage]
This value should be set to the motor nameplate
rated voltage.
Parameter Number
18
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
Drive Rated Volts
Minimum Value
25% of Drive Rated Voltage
Maximum Value
120% of Drive Rated Voltage
[Break Frequency]
This parameter sets a midpoint frequency on a
custom volts-per-Hertz curve. Combined with [Break
Voltage], this value determines the volts-per-Hertz
ratio between 0 and [Break Frequency].
Parameter Number
49
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Hertz / Hertz x 10
Factory Default
15.0 Hz
Minimum Value
0.0 Hz
Maximum Value
120.0 Hz
[Break Voltage]
Sets the voltage the drive will output at [Break
Frequency]. Combined with [Break Frequency], this
parameter determines the volts-per-Hertz pattern
between 0 and [Break Frequency].
Parameter Number
50
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
25% of Drive Rated Voltage
Minimum Value
0 Volts
Maximum Value
50% of Drive Rated Voltage
[Maximum Voltage]
This parameter sets the highest voltage the drive will
output.
Parameter Number
20
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
Drive Rated Volts
Minimum Value
25% of Drive Rated Voltage
Maximum Value
120% of Drive Rated Voltage