4–3
Start-Up
Apply Power
7. Apply AC power and control voltages to
the drive. The LCD Display should light
and display a drive status of “Stopped” and
an output frequency of “+0.00 Hz.”
If the drive detects a fault, a brief state-
ment relating to the fault will be shown on
the display. Record this information,
remove all power and correct the fault
source before proceeding. Refer to Chapter
6 for fault descriptions.
Stopped
+0.00 Hz
Reset Factory Defaults
or
or
8. Important: The remaining steps in this
procedure are based on factory default
parameter settings. If the drive has been
previously operated, parameter settings
may have been changed and may not be
compatible with this start-up procedure or
application. Drive status and fault
conditions may be unpredictable when
power is first applied.
To obtain proper results, the parameters
must be restored to factory default settings.
A. From the Status Display, press Enter
(or any key). “Choose Mode” will be
displayed.
B. Press the Increment (or Decrement)
key until “EEPROM” is displayed. If
EEProm is not in the menu,
programming is password protected.
Refer to Chapter 3 for Password
information.
C. Press Enter.
D. Press the Increment (or Decrement)
key until “Reset Defaults” is
displayed.
E. Press Enter to restore all parameters to
their original factory settings.
F. Press ESC. “Reprogram Fault” will
display.
G. Press the Stop key to reset the fault.
Important: If [Input Mode] was previously
set to a value other than “1,” cycle drive
power to reset.
Choose Mode
Display
Choose Mode
EEProm
EEProm
Reset Defaults
Choose Mode
EEProm
Reprogram Fault
F 48
Stopped
+0.00 Hz