5–24
Programming
[P Jump]
This value sets the slip or inertia compensation
amplitude of speed modulation.
Parameter Number
80
Parameter Type
Read and Write
Display Units / Drive Units
0.01 Hertz / 32767 = [Maximum Freq]
Factory Default
0.00 Hz
Minimum Value
0.00 Hz
Maximum Value
25% of [Maximum Freq]
[Sync Loss Sel]
This parameter allows selection of various sync loss
modes. The Sync Loss feature detects a
synchronous motor that is out of sync.
Parameter Number
201
Parameter Type
Read and Write
Factory Default
“Disabled”
Units
Display Drive
“Disabled” 0
Sync loss disabled
“Alarm” 1
Sync loss w/alarm to indicate loss
“Fault” 2
Fault will occur after
[Sync Loss Time]
[Sync Loss Time]
This parameter sets the amount of time a sync loss
condition will exist. When this time is exceeded, a
“Sync Loss Fault“ will occur.
Parameter Number
202
Parameter Type
Read and Write
Display Units / Drive Units
1.0 Sec / Seconds x 100
Factory Default
5.0 Sec
Minimum Value
1.0 Sec
Maximum Value
30.0 Sec
[Sync Loss Comp]
A compensation voltage designed to bring the motor
back into sync.
Parameter Number
203
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
0 Volts
Minimum Value
0 Volts
Maximum Value
25% of Drive Rated Volts
[Sync Loss Gain]
Adjusts the sensitivity level of sync loss detection. A
lower value means the drive will be less sensitive to
a loss of sync.
Parameter Number
199
Parameter Type
Read and Write
Display Units / Drive Units
None
Factory Default
40
Minimum Value
0
Maximum Value
100
[Enable Output]
The drive will operate normally when this parameter
is “Enabled.” When “Disabled” is selected, the drive
output will be disabled. In this state the drive
frequency can be changed instantaneously. When
re-enabled, the drive will output the voltage
corresponding to this new output frequency without
going through the accel/decel ramps. This is
typically used for reconnect to a rotating motor using
an external controller.
Parameter Number
216
Parameter Type
Read and Write
Factory Default
“Enabled”
Units
Display Drive
“Disabled” 0
“Enabled” 1
Feature Select