Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 103

5–37
Programming
This group of parameters contains binary masks for all control functions. The masks control
which adapters can issue control commands.
Masks
TB3
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Each mask contains a bit for each adapter.
Individual bits can be set to “Zero” to lockout
control by an adapter or set to “1” to permit an
adapter to have control.
With a Series A (version 3.0) or Series B HIM,
a Status description (bit ENUM) is displayed
on line 1.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Mask
Not Used
[Direction Mask]
This parameter controls which adapters can issue
forward/reverse commands.
Parameter Number
94
Parameter Type
Read and Write
Factory Default
01111110
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Start Mask]
This parameter controls which adapters can issue
start commands.
Parameter Number
95
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Jog Mask]
This parameter controls which adapters can issue
jog commands.
Parameter Number
96
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Reference Mask]
This parameter controls which adapters can select
an alternate reference; [Frequency Sel 1],
[Frequency Sel 2] or preset speeds.
Parameter Number
97
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Accel Mask]
This parameter controls which adapters can select
[Accel Time 1] and [Accel Time 2].
Parameter Number
98
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control
[Decel Mask]
This parameter controls which adapters can select
[Decel Time 1] and [Decel Time 2]
Parameter Number
99
Parameter Type
Read and Write
Factory Default
01111111
Units
Display Drive
“0” 0
Deny Control
“1” 1
Permit Control