Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 72
5–6
Programming
[4-20 mA Hertz]
This parameter displays the frequency command
present at analog current input terminals 4 & 6 of
TB2. This value is displayed whether or not this is
the active frequency command.
Parameter Number
140
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq
Factory Default
None
Minimum Value
0.00 Hz
Maximum Value
400.00 Hz
[0-10 Volt Hertz]
This parameter displays the frequency command
present at analog voltage input terminals 4 & 5 of
TB2. This value is displayed whether or not this is
the active frequency command.
Parameter Number
139
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq
Factory Default
None
Minimum Value
0.00 Hz
Maximum Value
400.00 Hz
[Pot Hertz]
This parameter displays the frequency command
present at remote pot terminals 1, 2 & 3 of TB2. This
value is displayed whether or not this is the active
frequency command.
Parameter Number
138
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq
Factory Default
None
Minimum Value
0.00 Hz
Maximum Value
400.00 Hz
[Pulse/Enc Hertz]
This parameter displays the frequency command
present at pulse input terminals 7 & 8 of TB2 or at
the encoder input terminals on TB3 (if present). This
value is displayed whether or not this is the active
frequency command.
Parameter Number
63
Parameter Type
Read Only
Display Units / Drive Units
0.01 Hertz / 32767 = Maximum Freq
Factory Default
None
Minimum Value
0.00 Hz
Maximum Value
400.00 Hz
[Heatsink Temp]
This parameter displays the heatsink temperature.
Parameter Number
70
Parameter Type
Read Only
Display Units / Drive Units
1
°
C / Deg. C
Factory Default
None
Minimum Value
0
Maximum Value
255
°
C
[Last Fault]
This parameter displays the last drive fault. It is
updated whenever a new fault occurs.
Parameter Number
4
Parameter Type
Read Only
Display Units / Drive Units
Fault Number / Fault Number
Factory Default
None
Minimum Value
None
Maximum Value
None
[Torque Current]
This parameter displays the amount of current that
is in phase with the fundamental voltage component.
It is the current that is actually producing torque.
Parameter Number
162
Parameter Type
Read Only
Display Units / Drive Units
0.1 Amp / 4096 = Rated Amps (Motoring)
Factory Default
None
Minimum Value
–200% Drive Rating
Maximum Value
+200% Drive Rating
Metering