beautypg.com

Rockwell Automation 1336 8A-48A Fiber Industry User Manual

Page 72

background image

5–6

Programming

[4-20 mA Hertz]

This parameter displays the frequency command
present at analog current input terminals 4 & 6 of
TB2. This value is displayed whether or not this is
the active frequency command.

Parameter Number

140

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[0-10 Volt Hertz]

This parameter displays the frequency command
present at analog voltage input terminals 4 & 5 of
TB2. This value is displayed whether or not this is
the active frequency command.

Parameter Number

139

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[Pot Hertz]

This parameter displays the frequency command
present at remote pot terminals 1, 2 & 3 of TB2. This
value is displayed whether or not this is the active
frequency command.

Parameter Number

138

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[Pulse/Enc Hertz]

This parameter displays the frequency command
present at pulse input terminals 7 & 8 of TB2 or at
the encoder input terminals on TB3 (if present). This
value is displayed whether or not this is the active
frequency command.

Parameter Number

63

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[Heatsink Temp]

This parameter displays the heatsink temperature.

Parameter Number

70

Parameter Type

Read Only

Display Units / Drive Units

1

°

C / Deg. C

Factory Default

None

Minimum Value

0

Maximum Value

255

°

C

[Last Fault]

This parameter displays the last drive fault. It is
updated whenever a new fault occurs.

Parameter Number

4

Parameter Type

Read Only

Display Units / Drive Units

Fault Number / Fault Number

Factory Default

None

Minimum Value

None

Maximum Value

None

[Torque Current]

This parameter displays the amount of current that
is in phase with the fundamental voltage component.
It is the current that is actually producing torque.

Parameter Number

162

Parameter Type

Read Only

Display Units / Drive Units

0.1 Amp / 4096 = Rated Amps (Motoring)

Factory Default

None

Minimum Value

–200% Drive Rating

Maximum Value

+200% Drive Rating

Metering