Programming
[Decel Time 1]
This value determines the time it will take the drive
to ramp from [Maximum Freq] to 0 Hz. The rate
determined by this value and [Maximum Freq] is
linear unless [S Curve Enable] is “Enabled.” It
applies to any decrease in command frequency
unless [Decel Time 2] is selected.
Parameter Number
8
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Second / Seconds x 10
Factory Default
10.0 Sec
Minimum Value
0.0 Sec
Maximum Value
6000.0 Sec
[Base Frequency]
This value should be set to the motor nameplate
rated frequency.
Parameter Number
17
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Hertz / Hertz x 10
Factory Default
60.0 Hz
Minimum Value
25.0 Hz
Maximum Value
400.0 Hz
[Base Voltage]
This value should be set to the motor nameplate
rated voltage.
Parameter Number
18
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
Drive Rated Volts
Minimum Value
25% of Drive Rated Voltage
Maximum Value
120% of Drive Rated Voltage
[Maximum Voltage]
This parameter sets the highest voltage the drive will
output.
Parameter Number
20
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
Drive Rated Volts
Minimum Value
25% of Drive Rated Voltage
Maximum Value
120% of Drive Rated Voltage
[Minimum Freq]
This parameter sets the lowest frequency the drive
will output.
Parameter Number
16
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Hertz / Hertz x 10
Factory Default
0.0 Hz
Minimum Value
0.0 Hz
Maximum Value
120.0 Hz
[Maximum Freq]
This parameter sets the highest frequency the drive
will output.
This parameter cannot be changed while the drive is
running.
Parameter Number
19
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Hertz / Hertz x 10
Factory Default
60.0 Hz
Minimum Value
25.0 Hz
Maximum Value
400.0 Hz
Standard Volts-per-Hertz Pattern
Voltage
0
0
Frequency
Motor Rated
Base Voltage
Base Frequency
Maximum Voltage
Maximum Frequency
Motor Rated
Setup