Rockwell Automation 1336 8A-48A Fiber Industry User Manual
Page 85
5–19
Programming
[Skip Freq 1-3]
These values, in conjunction with [Skip Freq Band],
create a range of frequencies at which the drive will
not continuously operate.
Parameter Number(s)
32-34
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz
Factory Default
400 Hz
Minimum Value
0 Hz
Maximum Value
400 Hz
[Skip Freq Band]
This parameter determines the band width around a
[Skip Frequency]. The actual band width is
2 x [Skip Freq Band] –– 1/2 the band above and 1/2
the band below the skip frequency.
Parameter Number
35
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz
Factory Default
0 Hz
Minimum Value
0 Hz
Maximum Value
15 Hz
Skip Frequency Band
e
vi
r
D
y
c
n
e
u
q
e
r
F
l
a
u
t
c
A
Frequency
Time
Skip Frequency
Command
Frequency
Skip Band
[Pulse/Enc Scale]
This parameter contains the scaling factor for both
pulse train inputs (TB2-7, 8) and encoder feedback
speed regulation (TB3 terminals 31-36).
1. Encoder Feedback Operation
Enter actual encoder pulses per revolution
2. Pulse Train Input
Scale
Factor
Incoming Pulse Rate (Hz)
Desired Command Freq.
Motor Poles
2
x
=
Parameter Number
46
Parameter Type
Read and Write
Display Units / Drive Units
Factor / Pulses per Rev
Factory Default
64 PPR
Minimum Value
1
Maximum Value
4096
Pulse Train Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336–MOD–N1 option outputs 64 Hz/Hz.
At full analog reference, the pulse output will
be 60 Hz x 64 Hz/Hz = 3840 pulses/sec.
Pulse/Enc Scale
3840 Hz
60 Hz
4 Poles
2
= 128
This value will create a command frequency of
60 Hz for full analog reference to the option.
=
x
[Speed Filter]
A digital filter that sets the time constant for a single
pole speed command filter. This filter is located after
the active speed source is selected and before skip
speeds are checked.
Parameter Number
175
Parameter Type
Read and Write
Display Units / Drive Units
NA / NA
Factory Default
10
Minimum Value
1
Maximum Value
100
[Analog Filter]
An analog filter that sets the time command for the
single pole analog speed input filter. The pot,
isolated mA, 4-20 mA and 0-10 volt inputs are
filtered.
Parameter Number
176
Parameter Type
Read and Write
Display Units / Units
NA / NA
Factory Default
20
Minimum Value
1
Maximum Value
100
Frequency Set